SPECIFICATION FOR STANDARD AMF PANEL 82.5 KVA

Cubicle type, base mounting control panel with hinged doors, un-drilled bottom gland plate, AL. Bus Bar and accommodating the following:

SWITCH GEARS:

  • » 130A, 4 Pole Contactor for ALTERNATOR with Thermal O/L relay
  • » 130A, 4 Pole Contactor for MAINS (OPTIONAL)

BACK-UP PROTECTION:

  • HRC fuse for short circuit protection

MICROPROCESSOR BASED AMF MODULE INCORPORATING:

Functions:

  • » Supply Failure Timer
  • » Restoration Timer
  • » 3 Impulse automatic engine Start / Stop logic
  • » Mains / Generator Voltage & Frequency Sensing.

Multifunction Meter & PCC 0301 with Scrolling Readings for

  • » Water Temperature/ Lube Oil Pressure
  • » Voltage / Ampere/ Frequency / kW / kVA
  • » Running-hour counter

Fault Indication (LED Type)

  • » Over / Under Speed
  • » Fails To Start
  • » Low Oil pressure
  • » Battery Charger Failure
  • » High Engine Temperature

Electronic kWH meter (Counter Display)

Current Transformers

Relay:
Earth Fault Relay (Electronic type)

Indications (LED):

  • DG ON, Load on DG
  • Mains ON, Load on Mains, Battery Charger ON

Push Buttons (AMF MODULE BY PASS MODE)

  • Engine START / STOP ( Provided on Engine Controller )
  • Generator Contactor CLOSE / TRIP
  • Mains Contactor CLOSE / TRIP (If provided)
  • Fault ACCEPT / RESET

BATTERY CHARGER:

  • SMPS Based Unit with inbuilt Auto/Manual & Float/Boost Facility
  • DC Voltmeter & Ammeter (Separate)

PLHO / 0712/RKS/ASN

PRODUCT SHOWCASE

  • Golden Wheat Field
    20 kVA : X2.7TG1
    Ready to use, silent, compact and light weight
  • Autumn
    140 kVA : QSB 5.9G1
    Latest technology product: Value for money

major installation

  • Golden Wheat Field
    Cnergy IT Park,
    2 X 1500 kVA + 1 X 1250 kVA - Mumbai
  • Autumn
    200 kVA - NTPC -
    Koldam Hydel Project